"""DC linearised power-flow constraints (zonal), with optional N-1.

PREP-SHOT's default transmission representation is a "transport" or
"pipe" model: net flow ``trans_export[z1,z2]`` is bounded by line
capacity, and that's it. There's no Kirchhoff voltage law, no loop
flow, no reactance -- power can flow whichever way the LP optimum
prefers. That's fine for capacity-expansion screening, where the
question is "where to build" rather than "what does the AC network
actually do."

When ``config.json.dc_parameters.is_dc_flow`` is ``true``, this module
adds the standard DC linearisation: for every connected zone pair
``(z1, z2)`` with a positive susceptance ``b[z1,z2]``, the **net** flow
between the two zones is locked to the phase-angle difference times the
susceptance:

.. math::

    \\text{trans\\_export}_{h,m,y,z_1,z_2}
      - \\text{trans\\_export}_{h,m,y,z_2,z_1}
    = b_{z_1,z_2} \\cdot
      (\\theta_{h,m,y,z_1} - \\theta_{h,m,y,z_2}) \\cdot \\Delta h

The capacity bound on each direction (``trans_export <= cap_lines_
existing``) carries over unchanged, which means the *thermal* limit
still applies but Kirchhoff is now enforced too. Loop flows on a
multi-zone network are no longer free.

N-1 security-constrained mode (v1.18+)
======================================

When ``dc_parameters.is_n1_secure`` is also ``true`` and
``transmission_contingencies.csv`` lists which lines to protect
against, the model is solved under a **preventive** security policy:
the same ``gen`` decision must be feasible in the base case AND in
every contingency where one listed line is out of service. For each
contingency ``c``, the module adds a parallel set of state variables
(``theta_c``, ``trans_export_c``) and constraints (DC flow with the
outaged line forced to zero, capacity bounds, demand balance with
contingency flows). ``gen`` and ``charge`` are NOT duplicated --
preventive policy means the same dispatch must work everywhere.

Inputs (all optional):

* ``transmission_susceptance.csv`` -- columns ``zone1, zone2, value``
  (one row per UNORDERED zone pair; the loader symmetrises to both
  directions). Units: MW per radian (so ``b * angle_diff`` is MW).
  Missing rows -> 0 (no constraint, equivalent to "no electrical
  connection between these zones").

* ``transmission_contingencies.csv`` -- columns ``zone1, zone2``,
  one line per contingency case. Each row removes the named line in
  one parallel solve. Empty file -> no contingencies, equivalent to
  ``is_n1_secure=false``.

Config:

* ``dc_parameters.is_dc_flow`` (bool, default false) -- enable/disable
  base-case DC flow.
* ``dc_parameters.reference_zone`` (str, optional) -- zone whose phase
  angle is pinned to 0. Defaults to the first zone in ``model.zone``.
* ``dc_parameters.is_n1_secure`` (bool, default false) -- adds N-1
  contingency constraints. Requires ``is_dc_flow=true``.

The phase-angle variable ``model.theta`` is bounded to ``[-pi, pi]``
for numerical stability; in practice DC OPF angles stay well within
``+/- pi/2``.

This module is LP-stable: no binaries, no new non-convexity.
"""
import math

import pyoptinterface as poi


[文档]class AddDCFlowConstraints: """DC linearised power-flow constraints, opt-in.""" def __init__(self, model: object) -> None: self.model = model if not model.params.get('is_dc_flow', False): return # Reference bus: use config override if given, else the first # zone the dataset declared. Pinning one phase angle anchors # the otherwise translationally-invariant theta solution. self.ref_zone = ( model.params.get('reference_zone') or model.zone[0] ) if self.ref_zone not in set(model.zone): raise ValueError( f"DC flow reference_zone={self.ref_zone!r} is not in " f"the model's zone set {sorted(model.zone)!r}." ) # Symmetrise the susceptance lookup: the CSV ships one row per # unordered pair, but the rule below queries by ordered pair. susc_raw = model.params.get('transmission_susceptance') or {} self.b = {} for key, val in susc_raw.items(): if not isinstance(key, tuple) or len(key) != 2: continue z1, z2 = key self.b[(z1, z2)] = val self.b[(z2, z1)] = val # Phase angle, bounded to +/- pi for numerical stability. DC # OPF rarely needs more than +/- pi/2, but pi gives slack. model.theta = model.add_variables( model.hour, model.month, model.year, model.zone, lb=-math.pi, ub=math.pi, ) model.dc_theta_ref_cons = poi.make_tupledict( model.hour, model.month, model.year, rule=self.theta_ref_rule, ) model.dc_flow_cons = poi.make_tupledict( model.hour, model.month, model.year, model.zone, model.zone, rule=self.flow_rule, ) # N-1 security-constrained mode (v1.18+). For each line listed # in transmission_contingencies.csv, build a parallel set of # state variables + constraints under that contingency. Same # `gen` decision must be feasible in every case (preventive # policy). if not model.params.get('is_n1_secure', False): return # ``contingencies`` arrives from the CSV loader as a pandas # DataFrame with columns ``zone1, zone2`` (table format). # Normalise to a list of unordered (z1, z2) tuples, # alphabetised so we can compare against the b-lookup keys. contingencies_raw = model.params.get('contingencies') zone_set = set(model.zone) pairs = [] if contingencies_raw is not None and hasattr(contingencies_raw, 'iterrows'): for _, r in contingencies_raw.iterrows(): a, b_ = str(r['zone1']), str(r['zone2']) if a in zone_set and b_ in zone_set and a != b_: pairs.append(tuple(sorted([a, b_]))) # De-duplicate while preserving order. seen = set() self.contingencies = [] for p in pairs: if p not in seen: seen.add(p) self.contingencies.append(p) if not self.contingencies: return contingency_idx = list(range(len(self.contingencies))) model.contingency_idx = contingency_idx # theta_c[h, m, y, z, c] -- phase angle in contingency c. model.theta_c = model.add_variables( model.hour, model.month, model.year, model.zone, contingency_idx, lb=-math.pi, ub=math.pi, ) # trans_export_c[h, m, y, z1, z2, c] -- flow per direction in # contingency c, mirroring the base-case trans_export shape. model.trans_export_c = model.add_variables( model.hour, model.month, model.year, model.zone, model.zone, contingency_idx, lb=0, ) # Reference bus per contingency. model.dc_theta_ref_c_cons = poi.make_tupledict( model.hour, model.month, model.year, contingency_idx, rule=self.theta_ref_c_rule, ) # DC flow eq per (line, contingency). model.dc_flow_c_cons = poi.make_tupledict( model.hour, model.month, model.year, model.zone, model.zone, contingency_idx, rule=self.flow_c_rule, ) # Capacity bound per (direction, contingency). model.dc_cap_c_cons = poi.make_tupledict( model.hour, model.month, model.year, model.zone, model.zone, contingency_idx, rule=self.cap_c_rule, ) # Per-(zone, contingency) demand balance: same gen + charge as # base case, but flows redistributed. model.demand_balance_c_cons = poi.make_tupledict( model.hour, model.month, model.year, model.zone, contingency_idx, rule=self.demand_balance_c_rule, )
[文档] def theta_ref_rule( self, h: int, m: int, y: int ) -> poi.ConstraintIndex: """Pin the reference zone's phase angle to 0.""" model = self.model return model.add_linear_constraint( model.theta[h, m, y, self.ref_zone], poi.Eq, 0 )
[文档] def flow_rule( self, h: int, m: int, y: int, z1: str, z2: str ) -> poi.ConstraintIndex: """Net flow = susceptance * angle difference * dt. Only emitted for ordered pairs ``(z1, z2)`` with ``z1 < z2`` and a positive susceptance, so each electrical line gets one constraint instead of two redundant ones. The capacity bound on each ``trans_export`` direction stays in place. """ if z1 >= z2: return None b = self.b.get((z1, z2), 0) if b == 0: return None model = self.model dt = model.params['dt'] lhs = ( model.trans_export[h, m, y, z1, z2] - model.trans_export[h, m, y, z2, z1] - b * dt * ( model.theta[h, m, y, z1] - model.theta[h, m, y, z2] ) ) return model.add_linear_constraint(lhs, poi.Eq, 0)
# ------------------------------------------------------------------ # N-1 contingency rules
[文档] def theta_ref_c_rule( self, h: int, m: int, y: int, c: int ) -> poi.ConstraintIndex: """Pin reference zone's phase angle to 0 in contingency c.""" model = self.model return model.add_linear_constraint( model.theta_c[h, m, y, self.ref_zone, c], poi.Eq, 0 )
[文档] def flow_c_rule( self, h: int, m: int, y: int, z1: str, z2: str, c: int ) -> poi.ConstraintIndex: """Per-line DC flow eq in contingency c. The outaged line ``self.contingencies[c]`` has its flow forced to zero (both directions). Every other line follows the same susceptance-times-angle-difference relation as the base case. """ if z1 >= z2: return None b = self.b.get((z1, z2), 0) if b == 0: return None out_pair = self.contingencies[c] # alphabetised tuple model = self.model dt = model.params['dt'] if (z1, z2) == out_pair: # Force both directions of the outaged line to zero. model.add_linear_constraint( model.trans_export_c[h, m, y, z1, z2, c], poi.Eq, 0 ) return model.add_linear_constraint( model.trans_export_c[h, m, y, z2, z1, c], poi.Eq, 0 ) lhs = ( model.trans_export_c[h, m, y, z1, z2, c] - model.trans_export_c[h, m, y, z2, z1, c] - b * dt * ( model.theta_c[h, m, y, z1, c] - model.theta_c[h, m, y, z2, c] ) ) return model.add_linear_constraint(lhs, poi.Eq, 0)
[文档] def cap_c_rule( self, h: int, m: int, y: int, z1: str, z2: str, c: int ) -> poi.ConstraintIndex: """Capacity bound on contingency-case flow. ``trans_export_c[h, m, y, z1, z2, c] <= cap_lines_existing[y, z1, z2]``. Same numeric bound as the base case -- ``gen`` is shared between base and contingency, so capacity stays consistent. """ model = self.model lhs = ( model.trans_export_c[h, m, y, z1, z2, c] - model.cap_lines_existing[y, z1, z2] ) return model.add_linear_constraint(lhs, poi.Leq, 0)
[文档] def demand_balance_c_rule( self, h: int, m: int, y: int, z: str, c: int ) -> poi.ConstraintIndex: """Power balance in contingency c. Same as the base-case ``power_balance_rule`` in ``demand.py``, but with contingency-case flows. ``gen`` and ``charge`` are the shared base-case decisions (preventive policy). """ model = self.model load = model.params['demand'] dt = model.params['dt'] eff = model.params['transmission_line_efficiency'] # Imports = sum of inbound flows weighted by line efficiency. imp_z = poi.quicksum( eff[z1, z] * model.trans_export_c[h, m, y, z1, z, c] for z1 in model.zone ) exp_z = poi.quicksum( model.trans_export_c[h, m, y, z, z1, c] for z1 in model.zone ) gen_z = poi.quicksum( model.gen[h, m, y, z, te] for te in model.zone_techs.get(z, []) ) storage_set = set(model.storage_tech) charge_z = poi.quicksum( model.charge[h, m, y, z, te] for te in model.zone_techs.get(z, []) if te in storage_set ) # Mirror the base-case load-shedding slack so contingency # power balance can use it too. demand_z = load[z, y, m, h] * dt if hasattr(model, 'lns'): demand_z = demand_z - model.lns[h, m, y, z] lhs = demand_z - (imp_z - exp_z + gen_z - charge_z) return model.add_linear_constraint(lhs, poi.Eq, 0)