"""DC linearised power-flow constraints (zonal), with optional N-1.
PREP-SHOT's default transmission representation is a "transport" or
"pipe" model: net flow ``trans_export[z1,z2]`` is bounded by line
capacity, and that's it. There's no Kirchhoff voltage law, no loop
flow, no reactance -- power can flow whichever way the LP optimum
prefers. That's fine for capacity-expansion screening, where the
question is "where to build" rather than "what does the AC network
actually do."
When ``config.json.dc_parameters.is_dc_flow`` is ``true``, this module
adds the standard DC linearisation: for every connected zone pair
``(z1, z2)`` with a positive susceptance ``b[z1,z2]``, the **net** flow
between the two zones is locked to the phase-angle difference times the
susceptance:
.. math::
\\text{trans\\_export}_{h,m,y,z_1,z_2}
- \\text{trans\\_export}_{h,m,y,z_2,z_1}
= b_{z_1,z_2} \\cdot
(\\theta_{h,m,y,z_1} - \\theta_{h,m,y,z_2}) \\cdot \\Delta h
The capacity bound on each direction (``trans_export <= cap_lines_
existing``) carries over unchanged, which means the *thermal* limit
still applies but Kirchhoff is now enforced too. Loop flows on a
multi-zone network are no longer free.
N-1 security-constrained mode (v1.18+)
======================================
When ``dc_parameters.is_n1_secure`` is also ``true`` and
``transmission_contingencies.csv`` lists which lines to protect
against, the model is solved under a **preventive** security policy:
the same ``gen`` decision must be feasible in the base case AND in
every contingency where one listed line is out of service. For each
contingency ``c``, the module adds a parallel set of state variables
(``theta_c``, ``trans_export_c``) and constraints (DC flow with the
outaged line forced to zero, capacity bounds, demand balance with
contingency flows). ``gen`` and ``charge`` are NOT duplicated --
preventive policy means the same dispatch must work everywhere.
Inputs (all optional):
* ``transmission_susceptance.csv`` -- columns ``zone1, zone2, value``
(one row per UNORDERED zone pair; the loader symmetrises to both
directions). Units: MW per radian (so ``b * angle_diff`` is MW).
Missing rows -> 0 (no constraint, equivalent to "no electrical
connection between these zones").
* ``transmission_contingencies.csv`` -- columns ``zone1, zone2``,
one line per contingency case. Each row removes the named line in
one parallel solve. Empty file -> no contingencies, equivalent to
``is_n1_secure=false``.
Config:
* ``dc_parameters.is_dc_flow`` (bool, default false) -- enable/disable
base-case DC flow.
* ``dc_parameters.reference_zone`` (str, optional) -- zone whose phase
angle is pinned to 0. Defaults to the first zone in ``model.zone``.
* ``dc_parameters.is_n1_secure`` (bool, default false) -- adds N-1
contingency constraints. Requires ``is_dc_flow=true``.
The phase-angle variable ``model.theta`` is bounded to ``[-pi, pi]``
for numerical stability; in practice DC OPF angles stay well within
``+/- pi/2``.
This module is LP-stable: no binaries, no new non-convexity.
"""
import math
import pyoptinterface as poi
[docs]class AddDCFlowConstraints:
"""DC linearised power-flow constraints, opt-in."""
def __init__(self, model: object) -> None:
self.model = model
if not model.params.get('is_dc_flow', False):
return
# Reference bus: use config override if given, else the first
# zone the dataset declared. Pinning one phase angle anchors
# the otherwise translationally-invariant theta solution.
self.ref_zone = (
model.params.get('reference_zone') or model.zone[0]
)
if self.ref_zone not in set(model.zone):
raise ValueError(
f"DC flow reference_zone={self.ref_zone!r} is not in "
f"the model's zone set {sorted(model.zone)!r}."
)
# Symmetrise the susceptance lookup: the CSV ships one row per
# unordered pair, but the rule below queries by ordered pair.
susc_raw = model.params.get('transmission_susceptance') or {}
self.b = {}
for key, val in susc_raw.items():
if not isinstance(key, tuple) or len(key) != 2:
continue
z1, z2 = key
self.b[(z1, z2)] = val
self.b[(z2, z1)] = val
# Phase angle, bounded to +/- pi for numerical stability. DC
# OPF rarely needs more than +/- pi/2, but pi gives slack.
model.theta = model.add_variables(
model.hour, model.month, model.year, model.zone,
lb=-math.pi, ub=math.pi,
)
model.dc_theta_ref_cons = poi.make_tupledict(
model.hour, model.month, model.year,
rule=self.theta_ref_rule,
)
model.dc_flow_cons = poi.make_tupledict(
model.hour, model.month, model.year, model.zone, model.zone,
rule=self.flow_rule,
)
# N-1 security-constrained mode (v1.18+). For each line listed
# in transmission_contingencies.csv, build a parallel set of
# state variables + constraints under that contingency. Same
# `gen` decision must be feasible in every case (preventive
# policy).
if not model.params.get('is_n1_secure', False):
return
# ``contingencies`` arrives from the CSV loader as a pandas
# DataFrame with columns ``zone1, zone2`` (table format).
# Normalise to a list of unordered (z1, z2) tuples,
# alphabetised so we can compare against the b-lookup keys.
contingencies_raw = model.params.get('contingencies')
zone_set = set(model.zone)
pairs = []
if contingencies_raw is not None and hasattr(contingencies_raw, 'iterrows'):
for _, r in contingencies_raw.iterrows():
a, b_ = str(r['zone1']), str(r['zone2'])
if a in zone_set and b_ in zone_set and a != b_:
pairs.append(tuple(sorted([a, b_])))
# De-duplicate while preserving order.
seen = set()
self.contingencies = []
for p in pairs:
if p not in seen:
seen.add(p)
self.contingencies.append(p)
if not self.contingencies:
return
contingency_idx = list(range(len(self.contingencies)))
model.contingency_idx = contingency_idx
# theta_c[h, m, y, z, c] -- phase angle in contingency c.
model.theta_c = model.add_variables(
model.hour, model.month, model.year, model.zone, contingency_idx,
lb=-math.pi, ub=math.pi,
)
# trans_export_c[h, m, y, z1, z2, c] -- flow per direction in
# contingency c, mirroring the base-case trans_export shape.
model.trans_export_c = model.add_variables(
model.hour, model.month, model.year, model.zone, model.zone,
contingency_idx,
lb=0,
)
# Reference bus per contingency.
model.dc_theta_ref_c_cons = poi.make_tupledict(
model.hour, model.month, model.year, contingency_idx,
rule=self.theta_ref_c_rule,
)
# DC flow eq per (line, contingency).
model.dc_flow_c_cons = poi.make_tupledict(
model.hour, model.month, model.year, model.zone, model.zone,
contingency_idx,
rule=self.flow_c_rule,
)
# Capacity bound per (direction, contingency).
model.dc_cap_c_cons = poi.make_tupledict(
model.hour, model.month, model.year, model.zone, model.zone,
contingency_idx,
rule=self.cap_c_rule,
)
# Per-(zone, contingency) demand balance: same gen + charge as
# base case, but flows redistributed.
model.demand_balance_c_cons = poi.make_tupledict(
model.hour, model.month, model.year, model.zone, contingency_idx,
rule=self.demand_balance_c_rule,
)
[docs] def theta_ref_rule(
self, h: int, m: int, y: int
) -> poi.ConstraintIndex:
"""Pin the reference zone's phase angle to 0."""
model = self.model
return model.add_linear_constraint(
model.theta[h, m, y, self.ref_zone], poi.Eq, 0
)
[docs] def flow_rule(
self, h: int, m: int, y: int, z1: str, z2: str
) -> poi.ConstraintIndex:
"""Net flow = susceptance * angle difference * dt.
Only emitted for ordered pairs ``(z1, z2)`` with ``z1 < z2``
and a positive susceptance, so each electrical line gets one
constraint instead of two redundant ones. The capacity bound
on each ``trans_export`` direction stays in place.
"""
if z1 >= z2:
return None
b = self.b.get((z1, z2), 0)
if b == 0:
return None
model = self.model
dt = model.params['dt']
lhs = (
model.trans_export[h, m, y, z1, z2]
- model.trans_export[h, m, y, z2, z1]
- b * dt * (
model.theta[h, m, y, z1] - model.theta[h, m, y, z2]
)
)
return model.add_linear_constraint(lhs, poi.Eq, 0)
# ------------------------------------------------------------------
# N-1 contingency rules
[docs] def theta_ref_c_rule(
self, h: int, m: int, y: int, c: int
) -> poi.ConstraintIndex:
"""Pin reference zone's phase angle to 0 in contingency c."""
model = self.model
return model.add_linear_constraint(
model.theta_c[h, m, y, self.ref_zone, c], poi.Eq, 0
)
[docs] def flow_c_rule(
self, h: int, m: int, y: int, z1: str, z2: str, c: int
) -> poi.ConstraintIndex:
"""Per-line DC flow eq in contingency c.
The outaged line ``self.contingencies[c]`` has its flow forced
to zero (both directions). Every other line follows the same
susceptance-times-angle-difference relation as the base case.
"""
if z1 >= z2:
return None
b = self.b.get((z1, z2), 0)
if b == 0:
return None
out_pair = self.contingencies[c] # alphabetised tuple
model = self.model
dt = model.params['dt']
if (z1, z2) == out_pair:
# Force both directions of the outaged line to zero.
model.add_linear_constraint(
model.trans_export_c[h, m, y, z1, z2, c], poi.Eq, 0
)
return model.add_linear_constraint(
model.trans_export_c[h, m, y, z2, z1, c], poi.Eq, 0
)
lhs = (
model.trans_export_c[h, m, y, z1, z2, c]
- model.trans_export_c[h, m, y, z2, z1, c]
- b * dt * (
model.theta_c[h, m, y, z1, c]
- model.theta_c[h, m, y, z2, c]
)
)
return model.add_linear_constraint(lhs, poi.Eq, 0)
[docs] def cap_c_rule(
self, h: int, m: int, y: int, z1: str, z2: str, c: int
) -> poi.ConstraintIndex:
"""Capacity bound on contingency-case flow.
``trans_export_c[h, m, y, z1, z2, c] <= cap_lines_existing[y,
z1, z2]``. Same numeric bound as the base case -- ``gen`` is
shared between base and contingency, so capacity stays
consistent.
"""
model = self.model
lhs = (
model.trans_export_c[h, m, y, z1, z2, c]
- model.cap_lines_existing[y, z1, z2]
)
return model.add_linear_constraint(lhs, poi.Leq, 0)
[docs] def demand_balance_c_rule(
self, h: int, m: int, y: int, z: str, c: int
) -> poi.ConstraintIndex:
"""Power balance in contingency c.
Same as the base-case ``power_balance_rule`` in ``demand.py``,
but with contingency-case flows. ``gen`` and ``charge`` are
the shared base-case decisions (preventive policy).
"""
model = self.model
load = model.params['demand']
dt = model.params['dt']
eff = model.params['transmission_line_efficiency']
# Imports = sum of inbound flows weighted by line efficiency.
imp_z = poi.quicksum(
eff[z1, z] * model.trans_export_c[h, m, y, z1, z, c]
for z1 in model.zone
)
exp_z = poi.quicksum(
model.trans_export_c[h, m, y, z, z1, c]
for z1 in model.zone
)
gen_z = poi.quicksum(
model.gen[h, m, y, z, te]
for te in model.zone_techs.get(z, [])
)
storage_set = set(model.storage_tech)
charge_z = poi.quicksum(
model.charge[h, m, y, z, te]
for te in model.zone_techs.get(z, [])
if te in storage_set
)
# Mirror the base-case load-shedding slack so contingency
# power balance can use it too.
demand_z = load[z, y, m, h] * dt
if hasattr(model, 'lns'):
demand_z = demand_z - model.lns[h, m, y, z]
lhs = demand_z - (imp_z - exp_z + gen_z - charge_z)
return model.add_linear_constraint(lhs, poi.Eq, 0)